Product Specification
Brand | HS Switchgear |
Condition | New |
Warranty | YES |
Product Descriptions
A market leader in 12kV switchgear, the Eclipse is designed to provide a lifetime of unrivalled service, bringing together one of the most advanced operating mechanisms available on the market today – the award winning magnetic actuator technology – with vacuum interruption and the simplicity of air insulation in a compact, fixed pattern design.
Appreciated throughout the distribution network and across every business sector, the Eclipse currently holds a dominant market position for indoor 12kV switchgear.
- Superior, proven Fit & Forget technology with minimal maintenance
- The fixed pattern design had the simplicity of air insulation and, with the low parts count (the total parts count has been reduced by a factor of x20 and the number of moving parts by a factor of x50), is more compact (500mm wide) than equivalent rated GIS equipment
- Environmentally friendly vacuum interrupters
- Internal Arc containment
- Superior operator safety with a fully interlocked design, animated front panel mimic and a front access cable test facility, ensuring secure but simple operation
- Voltage Presence Indication System (VPIS) is fitted as standard to all panels (circuit)
- Reliable control – supplied with an integral control module, providing indication, trip circuit supervision and self-diagnostics
- Customers choice of protection
DIMENSION (IN MM)
- Dimensions for a standard Eclipse feeder/incomer panel; (a) 1162 (b) 2165 (c) 500
- Dimensions for a standard Bus-section panel; (a) 1162 (b) 2165 (c) 1000
- Dimensions for a Busbar earthing switch; (c) 325
- Dimensions for a single panel with Busbar VT; (b) 2500
- Dimensions for top entry cable; One cable per phase - (a) 1482
- Three cables per phase - (a) 1812
ECLIPSE ENGINEERING DETAIL
- Sleeved busbars constructed from hard drawn, high conductivity copper, and vermin proof covered joints, 1 with normal current ratings up to 2000A. The busbar arrangement permits future expansion, at either end of 2 the switchboard.
- Fully interlocked, manually operated 3-position disconnector including circuit earth and front panel cable test access. The disconnector can be secured and 4 padlocked in all three positions: ‘on’, ‘off’ and ‘earth on/ test’, with its status indicated by animated front panel mimics.
- A single moulding supports the three phase vacuum interrupter assembly, magnetic actuator mechanism and 6 one-piece drive beam. 5
- The patented single coil magnetic actuator mechanism is based on a solenoid plunger, held in the tripped or closed position by permanent magnets.
- Three phase cast resin voltage transformer, with manually operated off-load disconnector on the primary circuit.
- Generous CT accommodation enables complex protection schemes to be catered for in a single panel, whilst still allowing for a metering provision. The CT designs are rated in keeping with the short time withstand level of the equipment and comply with IEC 60044-1.
UNIQUE FRONT ACCESS CABLE TESTING OPTION:
- Avoids any contact with Live cables or busbars.
- Eliminates the need for Opening of rear covers to access live cables.
- Provides secure & mechanically interlocked front access contacts points to connect cable test equipment.
- Colour coded and suitably labelled copper contacts eliminates risk of improper connections during testing live cables.