Product Specification
Brand | BERICA CAVI |
Condition | New |
Warranty | YES |
Product Descriptions
APPLICATION: Suitable for the transport of energy and the transmission of signals and controls in fire risk areas and with a lot of people like schools, offices, theaters, subways, hospitals, places of worship, shopping centers and places of public entertainment , when you need a mechanical protection against rodents, termites etc.
INSTALLATION: For fixed indoor and outdoor installation even in wet environments. They can be installed on wall and metal structures, on platforms, pipes, conduits and similar systems. Cable for direct and indirect burial.
EATURES | DESCRIPTION | STANDARD |
---|---|---|
Conductors: | annealed red copper cl.5 | CEI EN 60228 (Tab. 9) |
Insulation: | LSZH compound, G7 quality | CEI EN 50363 |
Cores colour: | CEI UNEL 00722 - HD 308 | |
Inner sheath: | LSZH compound, M1 quality | CEI EN 50363 |
Armour: | braid of galvanized steel | |
Outer sheath: | LSZH compound, M1 quality | CEI EN 50363 |
Outer sheath colour: | green RAL 6018 | |
Fire retardant: | CEI EN 60332-3-24 | |
Flame retardant: | CEI EN 60332-1-2 | |
Halogen free : | (< 0,5 mg/g - 0,5%) | CEI EN 50267-2-1/2 - IEC 60754-1/2 |
Low toxic gases emission: | (toxicity index < 2%) | CEI 20-37/4-0 |
Low smoke emission: | (trasmittance > 60%) | CEI EN 61034-2 |
DC resistance: | according to | CEI EN 60228 (Tab. 9) |
Current capacity: | CEI UNEL 35024/1 - CEI UNEL 35026 | |
Rated voltage Uo/U: | 0,6/1 kV | |
Max. voltage: | 1,2 kV | |
Testing voltage: | 4 kV | |
Max working temperature: | 90 °C | |
Short-circuit temperature: | 250 °C | |
Min. installation temperature: | 0 °C | |
Bending radius: | Ø x 14 | |
Max standard twisting (2x cable): | ≥ 10 twists/meter | |
Printing: | BERICA CAVI S.P.A. ITALY FG7OAM1 0,6/1 kV CEI 20-22 III cat. C CE Year/Lot - Type - 00000 m |