Product Specification
Brand | HELUKABEL |
Condition | New |
Warranty | YES |
Product Descriptions
Technical data
- XLPE-insulated power cables acc. to
DIN VDE 0276 part 620, HD 620 S2
and IEC 60502 - Temperature range
during installation up to -20°C - Operating temperature
max. +90°C - Short circuit temperature
+250°C (short circuit duration max. 5 s) - Nominal voltage
U0/U 6/10 kV, 12/20 kV, 18/30 kV - Operating voltage, 50 Hz
for 6/10 kV = max. 12 kV
for 12/20 kV = max. 24 kV
for 18/30 kV = max. 36 kV - Test voltage
for 6/10 kV = 21 kV
for 12/20 kV = 42 kV
for 18/30 kV = 63 kV- Minimum bending radius
15x cable Ø
- Minimum bending radius
Cable structure
- Bare copper conductor, to
DIN VDE 0295 cl.2, multi-wire,
BS 6360 cl.2, IEC 60228 cl.2 - Inner semi-conducting coating
- Core insulation of cross-linked polyethylene
(XLPE), compound type DIX8 to HD 620 S2 - Outer conductive layer extruded and per-
manently welded with the core insulation - Longitudinally watertight,
conductive wrapping - Screen: Braiding of copper wires with
one or two tapes applied helically - Longitudinally watertight wrapping
- Aluminium tape spliced with
PE sheath - Outer sheath of PE
compound type DMP2 to HD 620 S2 - Sheath colour: black