Product Specification
Brand | Aware Fire |
Capacity | 1000 |
Extinguishing Agent | strontium nitrate |
Hose Length (mm) | 86 |
Product Descriptions
- Name of Product: Wall Mount Type Aerosol Fire Extinguishing System
- Models: AW-QRR5GW/S,AW-QRR7.5GW/S, AW-QRR8GW/S, AW-QRR3GW/S
- Cargo Size: φ31*71 cm.
- Compound Quality: 3 kgs, 5 kgs, 7.5 kgs, 8 kgs, 10kgs.
- Protective Volume: 21m³, 35m³, 53m³, 57m³, 71m³.
- Design Density: 130 to 150 gram per cubic meters.
- Operation Volt: DC 3 to 24, AC 3 to 220.
- Activation Mode: Electric Start-up.
- Humidity: No more than 98%。
- Working Current: 1A/5ms.
- Maximum Safe Current: ≤150mA/5min
- Minimum Operation Current: ≥250mA/5ms
- Ambient Temperature: -20℃ to 55℃.
- Nozzle Location: Both left and right side.
- Material and Color: Iron Steel with Red Painting.
DESCRIPTION
Wall mount type aerosol fire extinguishing system is normally for some industrial projects, and for some bigger size of enclosure space, such as: computer rooms, data processing rooms, telecommunication rooms, big power generation rooms, Server Racks.
And for some enclosure warehouses, cable tunnels also can use aerosol system as a total system.
As one of China Top Ten Fire Suppression Enterprise in Mainland, We are able to offer with a one stop service for your requirement, we can develop, research and produce the product, we have own many patents for our products and brand, we also can provide with accessories and Fire Alarm Systems for your demand.
BASIC FEATURES
- It can cover some large size of enclosure space.
- The aerosol compound is clean without damage to Precision Equipment and Instruments at site.
- It takes no pressure to work, so it is safe for people to operate.
- Life span is very long, can reach above 10 years.
- Warranty Time: 1 to 2 years.
- Maintenance Free.
- Could be hanged on side wall and on ceiling and two directions to suppress fire.
- It is DIY easy in installation.
- CE, ROHS, ISO9001, ISO14001, ISO18001, GL, DNV, CCC, China Marine certificated, and will going to apply certificates of UL, FM200, BSI, KIWA, Active Fire, LPCB, GREEN LABEL, SNAP, ULC soon.
MAIN APPLICATION
- Computer room.
- Data Room.
- Server Room.
- Archives.
- Museums.
- Library.
- High-rise Building.
- Underground Pipe Gallery.
- UPS and EPS Room.
- Energy Storage Room.
AFTER SALES SERVICE
We have 1 more years warranty time for all the aerosol style fire extinguishing systems, within the warranty time if any damage that is not man-made can be replaced free of charge.
Please install and operate the device correctly as per our user instruction and keep the device in a dry storage place.
NOTE
- Never try to disassemble the aerosol device privately.
- Do not touch the red outer cylinder after releasing, because super hot over there, it may hurt you if so.
- Do the installation as Per Our INSTALLATION MANUAL offered together.
- Check that whether the installation accessories are all over there.
- Keep it in a dry and ventilation storage place.